Oil- immersed transformer series

S11 oil immersed transformer series

S(Z)9, S(Z)11, S(Z) 9-M, S(Z) 11-M, SH (B) 15 series oil-immersed transformers with the voltage of 35KV and below manufactured by us are new generation energy-saving products and are widely applied in the power system on the line of 35KV and below, and used for power transmission, transformation, distribution, power plant, power, lighting and HV/LV prefabricated substation.


Reserve this product for yourself




Product futures

  • Corrugated sheet or plate radiator oil tank, beautiful appearance.
  • New hanger plate structure, solving the problem of body “suspension”.
  • The transformer oil does not contact with air, so regular oil sample test (sealing type) is not necessary.
  • Equipped with self-locking nuts, no-suspended core structure, close fitting of body and oil tank; it can bear movement vibration and joint.
  • Corrugated sheet not only has cooling function, but also has “breathing” function. Tts elasticity can compensate the oil volume change caused by temperature change.
  • No oil needs to be changed in the normal service life, improving the safety and reliability of power grid operation.

Model meaning

image

S11-M-30-1600/10 Series Three-phase Two-Winding Off-Circuit-Tap-changing Distribution Transformer

Rated Capacity (kVA) Voltage combination
High Presure (kV)
High Voltage Low voltage(kV) Connexion symbol No-load loss (W) Load loss (W) No-load current (%) Short circuit impedance (%) The gauge (S) Size (s)
Length*width*height
30 100 600 2.1 4 400x400 780x435x895
50 130 870 2 4 400x400 885x480x945
63 150 1040 1.9 4 440x440 850x235x980
80 180 1250 1.8 4 400x400 865x565x1005
100 200 1500 1.6 4 400x400 890x615x1060
120 240 1800 1.5 4 400x400 910x670x1065
160 290 2200 1.4 4 550x550 890x685x1120
200 6/6.3/10/10.5/11 ±2x2.5% 0.4 Yyn0 330 2600 1.3 4 550x550 1190x670x1120
250 Dyn11 400 3050 1.2 4 550x550 1280x780x1180
315 480 3650 1.1 4 550x550 1270x690x1230
400 570 4300 1 4 550x550 1370x760x1300
500 680 5100 1 4 660x660 1450x810x1395
630 810 6200 0.9 4.5 660x850 1640x950x1360
800 980 7500 0.8 4.5 660x660 1680x970x1575
1000 1150 10300 0.7 4.5 820x820 1810x1100x1570
1250 1360 12000 0.6 4.5 820x820 1890x1160x1640
1600 1640 14500 0.6 4.5 820x820 1970x1220x1720

S11-50-3150/35 Series Three-Phase Two-Winding Off-Circuit- Tap-changing Distribution Transformer

Rated Capacity (kVA) Voltage combination
High Presure (kV)
High Voltage Low voltage(kV) Connexion symbol No-load loss (W) Load loss (W) No-load current (%) Short circuit impedance (%) The gauge (S) Size (s)
Length*width*height
50 170 1150 1.4 660x660 990x570x1250
100 240 1910 1.3 660x660 1040x590x1330
200 340 3150 1.05 660x660 1260x680x1570
250 400 3740 0.95 660x660 1350x730x1600
400 580 5440 0.95 660x660 1510x800x1700
500 680 6550 0.9 820x820 1580x890x1790
630 35 38.5 ±5%0.4 Yyn0 810 7820 0.9 0.65 820x820 1660x960x1860
800 970 9350 0.85 820x820 1890x1130x2160
1000 1160 11480 0.8 820x820 2150x1320x2280
1250 1370 13860 0.75 1070x1070 2250x1780x2520
1600 1660 16580 0.7 1070x1070 2320x1810x2700
2000 2030 18280 0.7 1070x1070 2430x1980x2810
2500 2450 19550 0.7 1070x1070 2520x2280x2940
3150 3010 22950 0.65 1070x1070 2650x2460x3150